AeroNode · Supervisory controllers
The supervisory controller you own outright.
AeroNode supervises BACnet and Metasys N2 equipment at the edge: logic, schedules, trends and alarms run locally, and every node is managed from a browser. No point licensing. No annual SMA.
- Quad-core 2.4 GHz
- 4 serial channels
- Dual Ethernet
- 2 BI / 2 BO
- Fanless · DIN rail
Models
Three form factors. One firmware.
Every AeroNode runs the same firmware and the same AeroView interface. Choose the serial configuration and form factor the job needs.
AeroNode 485
AN-485Four isolated RS-485 trunks in a fanless DIN-rail controller.
- 4× isolated RS-485
- 1 GbE + 2.5 GbE
- 2 BI / 2 BO
- 7–36 VDC
AeroNode 232
AN-232Two RS-485 trunks plus two RS-232 ports.
- 2× RS-485 + 2× RS-232
- 1 GbE + 2.5 GbE
- 2 BI / 2 BO
- 7–36 VDC
AeroNode Touch
AN-T10A complete AeroNode behind a 10.1-inch touchscreen.
- 10.1" IPS 1280×800
- 10-point capacitive touch
- 4× isolated serial
- 1 GbE
Serious headroom
A quad-core 2.4 GHz processor with 8 GB of ECC memory runs logic, trending and four field buses without breaking a sweat.
Four trunks, one controller
Four serial channels on every model: isolated RS-485 for MS/TP and N2, or a mix of RS-485 and RS-232. No add-on port modules to buy.
Secure by default
HTTPS out of the box, signed firmware with automatic recovery, login protection, and outbound-only encrypted connections to supervisors.
Nothing to license
No device or point tiers, no license files and no annual SMA. The capacity you need is the capacity you get.
AeroNode 485
Four isolated RS-485 trunks in a fanless DIN-rail controller.
The standard AeroNode for BACnet MS/TP and Metasys N2 buildings. Each isolated RS-485 channel runs its own trunk with a per-channel termination jumper, so one controller can supervise up to four field buses alongside BACnet/IP.
Specifications
Compute
- Processor
- Quad-core 64-bit Arm, 2.4 GHz
- Memory
- 8 GB with ECC
- Storage
- 32 GB eMMC; optional M.2 NVMe SSD up to 1 TB
- Real-time clock
- Battery-backed RTC
- Watchdog
- Hardware watchdog with automatic recovery
Communications
- Ethernet
- 2 independent ports: LAN1 1 GbE, LAN2 2.5 GbE
- Serial
- 4× isolated RS-485 (COM1–COM4), 120 Ω termination jumper per channel
- USB
- USB 3.2 and USB 2.0 host ports
- Wireless (option)
- Dual-band Wi-Fi 5 (802.11ac) + Bluetooth 5.0, external antenna
- Cellular (option)
- 4G LTE Cat-4 global-band modem with GNSS, Nano-SIM slot
I/O & power
- Binary inputs
- 2× isolated binary inputs (up to 36 VDC)
- Binary outputs
- 2× isolated solid-state (open-drain) outputs for interposing relays
- Power input
- 7–36 VDC, pluggable screw terminal (24 VDC nominal)
- Indicators
- Power, activity, network and user status LEDs; buzzer
Software
- Firmware
- AeroNode firmware with signed updates and automatic rollback
- User interface
- AeroView, HTML5 in any modern browser, served over HTTPS
- Field protocols
- BACnet/IP, BACnet MS/TP, Johnson Controls Metasys N2 (N2 Open)
- BACnet server
- Publishes selected points as BACnet/IP objects for third-party front ends
- Licensing
- No point or device licensing. No annual SMA.
Physical & environmental
- Enclosure
- Fanless aluminum alloy, passive cooling
- Mounting
- 35 mm DIN rail (clip included) or VESA 75 wall mount
- Dimensions
- Approx. 5.4 × 3.6 × 1.6 in (137 × 92 × 40 mm)
AeroNode 232
Two RS-485 trunks plus two RS-232 ports.
The same controller with a mixed serial configuration. COM3 and COM4 are isolated RS-485 trunks for BACnet MS/TP or Metasys N2. COM1 and COM2 are RS-232 ports for point-to-point serial equipment through Aero's RS-232 drivers. Everything else matches the AeroNode 485.
Specifications
Compute
- Processor
- Quad-core 64-bit Arm, 2.4 GHz
- Memory
- 8 GB with ECC
- Storage
- 32 GB eMMC; optional M.2 NVMe SSD up to 1 TB
- Real-time clock
- Battery-backed RTC
- Watchdog
- Hardware watchdog with automatic recovery
Communications
- Ethernet
- 2 independent ports: LAN1 1 GbE, LAN2 2.5 GbE
- Serial
- 2× RS-232 (COM1–COM2, TX/RX/GND); 2× isolated RS-485 (COM3–COM4) with termination jumpers
- USB
- USB 3.2 and USB 2.0 host ports
- Wireless (option)
- Dual-band Wi-Fi 5 (802.11ac) + Bluetooth 5.0, external antenna
- Cellular (option)
- 4G LTE Cat-4 global-band modem with GNSS, Nano-SIM slot
I/O & power
- Binary inputs
- 2× isolated binary inputs (up to 36 VDC)
- Binary outputs
- 2× isolated solid-state (open-drain) outputs for interposing relays
- Power input
- 7–36 VDC, pluggable screw terminal (24 VDC nominal)
- Indicators
- Power, activity, network and user status LEDs; buzzer
Software
- Firmware
- AeroNode firmware with signed updates and automatic rollback
- User interface
- AeroView, HTML5 in any modern browser, served over HTTPS
- Field protocols
- BACnet/IP, BACnet MS/TP, Johnson Controls Metasys N2 (N2 Open)
- BACnet server
- Publishes selected points as BACnet/IP objects for third-party front ends
- Licensing
- No point or device licensing. No annual SMA.
Physical & environmental
- Enclosure
- Fanless aluminum alloy, passive cooling
- Mounting
- 35 mm DIN rail (clip included) or VESA 75 wall mount
- Dimensions
- Approx. 5.4 × 3.6 × 1.6 in (137 × 92 × 40 mm)
AeroNode Touch
A complete AeroNode behind a 10.1-inch touchscreen.
The full AeroNode controller built into an optically bonded 10.1-inch capacitive display. Mount it on a mechanical-room wall, an equipment pad or a front desk to put AeroView where the people are.
Specifications
Display
- Panel
- 10.1-inch IPS, 1280 × 800, 178° viewing angle
- Touch
- 10-point capacitive, toughened glass, optically bonded
Compute
- Processor
- Quad-core 64-bit Arm, 2.4 GHz
- Memory
- 8 GB with ECC
- Storage
- 32 GB eMMC; optional M.2 NVMe SSD (2230–2280) up to 1 TB
- Real-time clock
- Battery-backed RTC
- Watchdog
- Hardware watchdog with automatic recovery
Communications
- Ethernet
- 1× 1 GbE
- Serial
- 4 isolated serial channels
- USB
- USB 3.2 and USB 2.0 host ports
- Wireless (option)
- Dual-band Wi-Fi 5 (802.11ac) + Bluetooth 5.0
- Cellular (option)
- 4G LTE Cat-4 global-band modem with GNSS, Nano-SIM slot
I/O & power
- Binary inputs
- 2× isolated binary inputs (up to 36 VDC)
- Binary outputs
- 2× isolated solid-state (open-drain) outputs for interposing relays
- Power input
- 7–36 VDC, pluggable screw terminal (24 VDC nominal)
Software
- Firmware
- AeroNode firmware with signed updates and automatic rollback
- User interface
- AeroView, HTML5 in any modern browser, served over HTTPS
- Field protocols
- BACnet/IP, BACnet MS/TP, Johnson Controls Metasys N2 (N2 Open)
- BACnet server
- Publishes selected points as BACnet/IP objects for third-party front ends
- Licensing
- No point or device licensing. No annual SMA.
Physical & environmental
- Enclosure
- Fanless aluminum alloy, passive cooling
- Mounting
- Rear VESA-pattern mount
- Dimensions
- Approx. 9.9 × 6.7 × 1.8 in (250 × 170 × 45 mm)
Options & ordering
Configured at the factory. Tested before it ships.
Add wireless, cellular or extra storage to any model. The part number spells out exactly what's in the box.
Wi-Fi & Bluetooth
Dual-band radio with an external antenna, for commissioning or sites without a wired LAN.
- None
- Wi-Fi 5 + Bluetooth 5.0 · Dual-band 802.11ac, external antennaW
Cellular modem
Out-of-band connectivity to AeroConnect when the building network can't be used. SIM card not included.
- None
- 4G LTE Cat-4 + GNSS · Global bands, 150/50 Mbps, Nano-SIM slot, external antennasL
Expandable storage
Adds an M.2 NVMe SSD (2230/2242) for long-term trend history and local backups. The system boots from eMMC.
- Standard · 32 GB eMMC
- + 256 GB NVMe SSDN256
- + 512 GB NVMe SSDN512
- + 1 TB NVMe SSDN1T
Reading a part number
AN-485-WL-N512
AeroNode 485 with Wi-Fi (W) and LTE (L), plus a 512 GB NVMe SSD. Base models: AN-485, AN-232 and AN-T10.
Dealer pricing and configuration are available in the dealer portal.
FAQ
AeroNode questions, answered.
Does an AeroNode need a software license?
No. AeroNode firmware has no device or point limits and no license files, and firmware updates are included. There is no annual software maintenance agreement.
What power does it need?
AeroNode runs on 7–36 VDC (24 VDC nominal) through a pluggable screw terminal. In panels that only provide 24 VAC, add a DIN-rail 24 VDC power supply.
Can AeroNode work alongside our existing front end?
Yes. The built-in BACnet server publishes the points you choose as BACnet/IP objects, so an existing Niagara, Metasys or other BACnet workstation can read and command them during a phased migration.
How do firmware updates work?
Install signed firmware releases from the node's settings, on site or remotely through AeroConnect. The node verifies each release before installing it, and automatically restores the previous version if the new one fails to start.
What is the difference between the 485 and the 232?
Only the serial configuration. The AeroNode 485 has four isolated RS-485 channels. The AeroNode 232 has two RS-232 ports (COM1–COM2) and two isolated RS-485 channels (COM3–COM4).
Which protocols can the serial ports run?
The serial ports are driver-agnostic: each protocol is an Aero driver that runs in its own supervised process. BACnet MS/TP and Metasys N2 (N2 Open) ship today. Our goal is to support the open RS-485 and RS-232 protocols found in buildings, with Modbus RTU and RS-232 device drivers next on the roadmap. New drivers arrive as signed firmware updates.
Which options can be added?
Every model can be ordered with dual-band Wi-Fi 5 + Bluetooth, a global 4G LTE Cat-4 modem with GNSS, and an M.2 NVMe SSD for long-term trend storage. Options are factory-installed and tested before shipment.